p29626[0...n] Cavitation protection threshold / Cavi thresh
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: -
Min:
0.00 [%]
Max:
200.00 [%]
Factory setting:
40.00 [%]
Description: Defines the feedback threshold (as a percentage) for triggering a fault/alarm.
p29627[0...n] Cavitation protection time / Cavi time
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
1 [s]
Max:
65000 [s]
Factory setting:
30 [s]
Description: Sets the time for which cavitation conditions have to be present before a fault/alarm is triggered.
r29629.0...2 CO/BO: Status word: application / App status word
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status word for application:
bit 0:
= 1, pipe filling is active;
= 0, pipe filling is not active.
bit 2/1:
= 0/1, condesation protection is active;
= 1/1, frost protection is active;
= 0/0, frost and condensation protections are not active;
= 1/0, not used.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Pipe filling Active Inactive -
01 Condensation protection Active Inactive -
02 Frost protection Active Inactive -
p29630 Keep-running operation enable / KeepRun
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description: Sets the signal source to enable converter keep-running operation. This attempts to prevent the converter from
tripping by enabling all possible existing de-rating features and the automatic restart function.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 929