EasyManua.ls Logo

Siemens SINAMICS G120X - CO: Counter for Fault Buffer Changes; Fault Buff Change; Fault Code; Fault Code; Fault Code List; Fault Code List

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
r0944 CO: Counter for fault buffer changes / Fault buff change
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8060
Min:
-
Max:
-
Factory setting:
-
Description: Display and connector output for the counter for changes of the fault buffer.
This counter is incremented every time the fault buffer changes.
Recommendation: Used to check whether the fault buffer has been read out consistently.
Dependency: See also: r0945, r0947, r0948, r0949, r2109
r0945[0...63] Fault code / Fault code
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8060
Min:
-
Max:
-
Factory setting:
-
Description: Displays the numbers of faults that have occurred.
Dependency: See also: r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
NOTICE
The properties of the fault buffer should be taken from the corresponding product documentation.
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0] --> actual fault case, fault 1
. . .
r0945[7], r0949[7], r0948[7], r2109[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8] --> 1st acknowledged fault case, fault 1
. . .
r0945[15], r0949[15], r0948[15], r2109[15] --> 1st acknowledged fault case, fault 8
. . .
r0945[56], r0949[56], r0948[56], r2109[56] --> 7th acknowledged fault case, fault 1
. . .
r0945[63], r0949[63], r0948[63], r2109[63] --> 7th acknowledged fault case, fault 8
r0946[0...65534] Fault code list / Fault code list
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8060
Min:
-
Max:
-
Factory setting:
-
Description: Lists the fault codes stored in the drive unit.
The indices can only be accessed with a valid fault code.
Dependency: The parameter assigned to the fault code is entered in r0951 under the same index.
Parameters