EasyManua.ls Logo

Siemens SINAMICS G120X - Fault Buffer; Faults, Alarm Buffer and Alarm History

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.5 Faults, alarm buffer and alarm history
Overview
A fault generally indicates that the converter can no longer maintain the operation of the motor.
The extended diagnostics have a fault buffer and a fault history, in which the converter stores
the most recent faults.
Function description
Faults have the following properties:
In general, a fault leads to the motor being switched off.
A fault must be acknowledged.
Faults are displayed as follows:
Display via the fieldbus
Display on the operator panel with Fxxxxx
Display on the converter via the LED RDY
Display via SINAMICS G120 Smart Access
Fault buffer
2OG
1HZ
)DXOWFRGH)DXOWYDOXH)DXOWWLPHUHFHLYHG)DXOWWLPHUHPRYHG
'D\V'D\V
U>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
>@
U>@U>@U>@U>@U>@U>@
,IORDWPVPV
Figure 9-3 Fault buffer
The converter saves incoming faults in the fault buffer. A fault includes a fault code, a fault
value, and two fault times:
Fault code: r0945
The fault code and fault value describe the cause of the fault.
Fault value: r0949 in fixed-point format "I32", r2133 in floating-point format "Float"
Fault time received = r2130 + r0948
Fault time removed = r2136 + r2109
The converter takes its internal time calculation to save the fault times.
System runtime (Page 962)
Up to 8 faults can be saved in the fault buffer.
Warnings, faults and system messages
9.5 Faults, alarm buffer and alarm history
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 967

Table of Contents

Other manuals for Siemens SINAMICS G120X

Related product manuals