4: U/f control with linear characteristic and ECO
7: U/f control for a parabolic characteristic and ECO
20: Speed control (encoderless)
Dependency: For Standard Drive Control (p0096 = 1), settings p1300 = 0, 2 are possible, for Dynamic Drive Control (p0096 = 2) only
p1300 = 20 can be set.
Only operation with U/f characteristic is possible if the rated motor speed is not entered (p0311).
See also: p0300, p0311, p0500
NOTICE
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for the
ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note
For motors, type p0300 = 6 and 6xx, operation with U/f control is only recommended for diagnostic purposes.
p1300[0...n] Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C2(1), T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6300, 6301,
6851, 8012
Min:
0
Max:
20
Factory setting:
20
Description: Sets the open and closed-loop control mode of a drive.
Value: 0: U/f control with linear characteristic
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
4: U/f control with linear characteristic and ECO
7: U/f control for a parabolic characteristic and ECO
20: Speed control (encoderless)
Dependency: For Dynamic Drive Control (p0096 = 2), only p1300 = 20 can be set.
Only operation with U/f characteristic is possible if the rated motor speed is not entered (p0311).
See also: p0300, p0311, p0500
NOTICE
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for the
ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note
For motors, type p0300 = 14, operation with U/f control is only recommended for diagnostic purposes.
p1302[0...n] U/f control configuration / U/f config
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description: Sets the configuration for the U/f control.
Bit field: Bit Signal name 1 signal 0 signal FP
Parameters
7.2 Parameter list
SINAMICS G120X converter
668 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC