Note
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g. down
ramps, ramp-function generator, motor potentiometer).
The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0310, p0311, p0322.
The following limits are always effective for p1082:
p1082 <= 60 x minimum (15 x p0310, 550 Hz) / r0313
p1082 <= 60 x maximum power unit pulse frequency / (k x r0313), with k = 12 (vector control), k = 6.5 (U/f control)
During automatic calculation (p0340 = 1, p3900 > 0), the parameter value is assigned the maximum motor speed
(p0322). For p0322 = 0 the rated motor speed (p0311) is used as default (pre-assignment) value. For induction motors,
the synchronous no-load speed is used as the default value (p0310 x 60 / r0313).
For synchronous motors, the following additionally applies:
During automatic calculation (p0340, p3900), p1082 is limited to speeds where the EMF does not exceed the DC link
voltage.
p1082 is also available in the quick commissioning (p0010 = 1); this means that when exiting via p3900 > 0, the value
is not changed.
p1082[0...n] Maximum speed / n_max
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 1 Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: C2(1), T Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3020, 3050,
3070
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
1500.000 [rpm]
Description: Sets the highest possible speed setpoint.
Dependency: The maximum speed is limited to: p1082 <= 60 x 150 Hz / r0313
See also: p0230, p0310, r0313, p0322
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g. down
ramps, ramp-function generator, motor potentiometer).
The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0310, p0311 and p0322 (p0310 x 60 / r0313, for p0322 = 0).
p1083[0...n] CO: Speed limit in positive direction of rotation / n_limit pos
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
210000.000 [rpm]
Description: Sets the maximum speed for the positive direction.
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Parameters
7.2 Parameter list
SINAMICS G120X converter
626 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC