EasyManua.ls Logo

Siemens SINAMICS G120X - Fault Codes and Alarm Codes; Internal Software Error; List of Fault Codes and Alarm Codes; Overview of Faults and Alarms

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.6 List of fault codes and alarm codes
9.6.1 Overview of faults and alarms
Overview
A message comprises a letter followed by the relevant number.
The letters have the following meaning:
A . . . . Alarm code . . . .
F . . . . Fault code . . . .
N . . . . No report or internal message
9.6.2 Fault codes and alarm codes
All objects: G120X_DP, G120X_PN, G120X_USS
F01000 Internal software error
Reaction: OFF2
Acknowledge: POWER ON
Cause: An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - evaluate fault buffer (r0945).
- carry out a POWER ON (switch-off/switch-on) for all components.
- if required, check the data on the non-volatile memory (e.g. memory card).
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
F01001 FloatingPoint exception
Reaction: OFF2
Acknowledge: POWER ON