Table 4-10 Overview of default settings, Part 2/2
Default setting (macro)
Terminal 48 49 51
1)
52
1)
54
1)
55
1)
57
3)
AI 0 - - - Setpoint local - Setpoint local -
AI 1 PID actual
value
PID actual
value
- - - - -
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1
2)
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
DI 0 ON/OFF2 ON/OFF2 ON/OFF2 ON/OFF2 lo‐
cal
ON/OFF2 ON/OFF2 lo‐
cal
Jogging 1
DI 1 Service pump
1
Service pump
1
- ON/OFF2 re‐
mote
- ON/OFF2 re‐
mote
Jogging 2
DI 2 Service pump
2
Service pump
2
- - - - -
DI 3 - Service pump
3
- - - - -
DI 4 manual ↔ au‐
to
manual ↔ au‐
to
- local ↔ remote - local ↔ remote local ↔ remote
DI 5 Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
DO 0 Fault Fault Fault Fault Fault Fault Fault
DO 1 Operation Pump 1 Operation Operation Operation Operation Operation
DO 2
2)
Pump 1 Pump 2 Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
DO 3
2)
Pump 2 Pump 3 Alarm Alarm Alarm Alarm Alarm
Fieldbus - - Modbus RTU Modbus RTU USS USS PROFINET
or PROFIBUS
1)
For converters with USS fieldbus interfaces
2)
With I/O Extension Module
3)
For converters with PROFIBUS or PROFINET interfaces
Function description
Default setting (macro) 41: "Analog control"
"Analog control" is the factory setting for converters with RS 485 fieldbus interfaces.
Wiring
4.2 Control interfaces
SINAMICS G120X converter
108 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC