16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter calculation Yes No -
18 After motID direct transition into operation Yes No -
19 After MotID automatically save results Yes No -
20 Estimate cable resistance Yes No -
21 Calibrating the output voltage measurement Yes No -
22 Only identify circle Yes No -
23 Deactivate circle identification Yes No -
24 Circle identification with 0 and 90 degrees Yes No -
26 Measure with long cable Yes No -
Dependency: See also: r3925
Note
The parameter is a copy of p1909.
r3928[0...n] Rotating measurement configuration / Rot meas config
Access level: 3 Calculated: CALC_MOD_ALL Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Successfully completed component of the last rotating measurement carried out.
Bit field: Bit Signal name 1 signal 0 signal FP
01 Saturation characteristic identification Yes No -
02 Moment of inertia identification Yes No -
03 Re-calculates the speed controller parameters Yes No -
04 Speed controller optimization (vibration test) Yes No -
05 q leakage inductance ident. (for current controller adaptation) Yes No -
11 Do not change the controller parameters during the
measurement
Yes No -
12 Measurement shortened Yes No -
13 After measurement direct transition into operation Yes No -
14 Calculate speed actual value smoothing time Yes No -
Dependency: See also: r3925
Note
The parameter is a copy of p1959.
r3929[0...n] Motor data identification modulated voltage generation / MotID U_gen mod
Access level: 4 Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Configuration of voltage generation for the various MotID sections in the case of the most recent successful MotID.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Wobble U_generate to determine dead-time correction Yes No -
01 Wobble U_generate to determine stator resistance Yes No -
02 Wobble U_generation to determine rotor time constant Yes No -
03 Wobble U_generation to determine leakage inductance Yes No -
Parameters
7.2 Parameter list
SINAMICS G120X converter
848 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC