Frame
size
Rated
power
[kW] (NEC
[hp])
Rated in‐
put cur‐
rent [A]
(NEC
600 V)
Rated output
current [A]
(NEC 600 V)
Power
[kW]
(NEC
[hp])
Input cur‐
rent [A]
(NEC
600 V)
Output
current
[A] (NEC
600 V)
Power loss (kW) Weight (kg)
Based on Low Overload Based on High Overload With‐
out fil‐
ter
With fil‐
ter
With‐
out fil‐
ter
With fil‐
ter
FSJ 500 (---) 540 (591) 520 (546) 450 (450) 461 (501) 444 (482) -- 8.13 -- 236
560 (600) 602 (665) 580 (610) 500 (500) 494 (543) 476 (523) -- 8.83 -- 236
630 (700) 675 (737) 650 (679) 560 (500) 552 (602) 532 (580) -- 9.94 -- 246
*
For systems according to UL: 500 V ... 600 V
--- not applicable
Technical data
11.4 Technical data dependent on the power
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 1091