EasyManua.ls Logo

Siemens SINAMICS G120X - Page 115

Siemens SINAMICS G120X
1148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting Parameter Characteristics Setting Parameter
Default setting
43
p0015 = 43
$,
Q
PLQ
PLQ
999
$,
Q


999
Q
$2
P$
P$
PLQ
PLQ
,
$2
P$
P$
$$
DI 0
ON/OFF1
OFF2
DI 1
DI 2
DI 4
DI 5
p29652[0] = 722.0
p29650[0] = 0
p0840[0] = 29659.0
p0844[0] = 29659.1
p29543[0] = 722.1
p29543[1] = 722.2
p2200 = 722.4
p2104[0] = 722.5
AI 0 p2253[0] =
755[0]
p1070[0] =
755[0]
AI 1 p2264[0] =
755[1]
AO 0 p0771[0] = 21
AO 1 p0771[1] = 27 Multi-pump con‐
trol
p29520 = 1
p29521 = 2
p29539 = 1
p29540 = 1
DO 0
DO 1
DO 2
DO 3
p0730 = 52.3
p0731 = 52.2
p0732 = 29529.0
p0733 = 29529.1
Procedure for changing p0015 with the BOP-2 operator panel:
→ SETUP → … → MAc PAr → P15 = X AI 2XP → … → FINISH
Wiring
4.2 Control interfaces
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 113

Table of Contents