Procedure for FSH and FSJ
1. Set p0010 = 2.
2. Set the forming duration p3380.
Storage time from the production date Recommended forming duration
1 ... 2 years 1 hour
2 ... 3 years 2 hours
> 3 years 8 hours
For p3380 > 0, with alarm A07391, the converter signals that at the next ON command, DC
link forming starts.
3. Switch on the motor, e.g. from an inserted operator panel.
4. Wait for the forming time to elapse. r3381 indicates the remaining time.
If the line voltage is switched off before forming has been completed, then you have to form
the DC link again.
5. The converter sets p3380 = 0.
6. Set p0010 = 0.
You have formed the DC link.
❒
Parameter
Parameter Description Factory setting
p0010 Drive commissioning parameter filter 0
p3380 Forming activation/duration 0 h
r3381 Remaining forming time - h
r3382 Forming status word -
Commissioning
5.3 Preparing for commissioning
SINAMICS G120X converter
156 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC