If the converter is not running and the protection signal becomes active, protection measure is
applied as follows:
● If frost protection speed p29623 ≠ 0 (default 0), frost protection is activated by applying the
specified speed to the motor.
● If frost protection speed p29623 = 0 and condensation protection current p29624 ≠ 0,
condensation protection is activated by applying the specified current to the motor.
Parameters
Number Name Factory setting
p29622 BI: Frost protection enable 0
p29624 Condensation protection current 30%
For more information about the parameters, see Chapter "Parameters (Page 467)".
Advanced commissioning
6.4 Pump control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 319