Function description
After the pipe filling is enabled, you can select from the following two filling modes:
Time mode: p29611 = 0
The converter fills the pipe with a low speed for a specified time (p29613) and then changes
the speed to the setpoint.
3LSHILOOLQJ
VSHHG
6SHHG
3LSHILOOLQJWLPH
2SHUDWLRQ
W
S
S
Pressure mode: p29611 = 1
The converter fills the pipe according to the PID feedback from the pressure sensor. The
filling stops when the actual pressure (r2272) the threshold (p29614) for a specified time
(p29615).
3UHVVXUH
3LSHILOOLQJ
WKUHVKROG
3LSHILOOLQJ
VSHHG
6SHHG
2SHUDWLRQ
3LSHILOOLQJPRQLWRULQJWLPH
S
W
S
W
S
Note
Priority of deragging and pipe filling
The priority of functions is as follows: deragging > pipe filling.
Advanced commissioning
6.4 Pump control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 325