Maximum permissible motor cable length (Page 82)
NOTICE
Damage to the output reactor by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using the output reactor is 4 kHz or 2 kHz
(for FSH/FSJ). The output reactor can be damaged if the pulse frequency is exceeded.
When using an output reactor, the pulse frequency of the converter must not exceed 4 kHz
or 2 kHz (for FSH/FSJ).
NOTICE
Damage to the output reactor if it is not activated during commissioning
The output reactor may be damaged if it is not activated during commissioning.
Activate the output reactor during commissioning via parameter p0230.
Activate the output reactor during commissioning according to the electric specifications.
Article number
Converter frame size Rated power (kW) Output reactor
400 V converters
FSD 18.5 6SL3202-0AE23-8CA0
22 ... 37 6SE6400-3TC07-5ED0
FSE 45 ... 55 6SE6400-3TC14-5FD0
FSF 75 ... 90
110 6SL3000-2BE32-1AA0
132 6SL3000-2BE32-6AA0
FSG 160 6SL3000-2BE33-2AA0
200 6SL3000-2BE33-8AA0
250 6SL3000-2BE35-0AA0
FSH 315 6SL3000-2AE36-1AA0
355 ... 400 6SL3000-2AE38-4AA0
FSJ 450 ... 500 6SL3000-2AE41-0AA0
560 6SL3000-2AE41-4AA0
690 V converters
FSD 3 … 18.5 JTA:TEU2532-0FP00-4EA0
22 … 37 JTA:TEU9932-0FP00-4EA0
FSE 45 … 55 JTA:TEU9932-0FS00-0EA0
FSF 75 … 90 JTA:TEU9932-1FC00-1BA0
110 … 132 JTA:TEU9932-0FV00-1BA0
FSG 160 … 250 JTA:TEU4732-0FA00-0BA0
Description
2.6 Optional components
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC 37