Figure 6-105 Line contactor control via DO 2 with feedback signal via DI 3
If the line contactor feedback signal is not available for longer than the time set in p0861, the
converter signals fault F07300.
Parameters
Number Name Factory setting
r0046.0…n CO/BO: Missing enable signals -
p0860 BI: Line contactor feedback signal 863.1
p0861 Line contactor monitoring time 100 ms
r0863.0…1 CO/BO: Drive coupling status word / control word -
p0867 Power unit main contactor hold time after OFF1 50 ms
p0869 Configuration sequence control 0000 bin
p0870 BI: close main contactor 0
More information is provided in the parameter list.
Advanced commissioning
6.10 Energy saving
SINAMICS G120X converter
452 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC