p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / Enable RFG
G120X_DP,
G120X_PN
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501
Min:
-
Max:
-
Factory setting:
[0] 2090.4
[1] 1
[2] 2090.4
[3] 2090.4
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enable ramp-function generator.
Dependency: See also: r0054, p1141, p1142
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / Enable RFG
G120X_USS Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enable ramp-function generator.
Dependency: See also: r0054, p1141, p1142
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1141[0...n] BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
G120X_DP,
G120X_PN
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501
Min:
-
Max:
-
Factory setting:
[0] 2090.5
[1] 1
[2] 2090.5
[3] 2090.5
Parameters
7.2 Parameter list
SINAMICS G120X converter
638 Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC