PT29
*TOP3
Function
selection T-3
_ _ _ x (BIN): DOG (Proximity dog) polarity selection
Profile mode, cyclic synchronous mode and point table method
0: Dog detection with off
1: Dog detection with on
Indexer method
0: Dog detection with on
1: Dog detection with off
_ _ x _ (BIN): For manufacturer setting
_ x _ _ (BIN): For manufacturer setting
x _ _ _ (BIN): For manufacturer setting
Convert the setting value into hexadecimal as follows.
0
Initial value
BIN HEX
Setting
0
0
00
0
DOG (Proximity dog) polarity selection
0
0
PT34
**PDEF
Point table
default
Use this parameter when initializing point tables.
A point table will be the following status by being initialized.
Point table: All "0"
Initialize the point tables with the following procedures:
1) Set "5001h" to this parameter.
2) Cycle the power of the driver.
After the driver power is on, the initialization completes in about 20 s. After the
initialization, the setting of this parameter will be "0000h" automatically.
This function will be enabled in the point table method.
PT35
*TOP5
Function
selection T-5
Superimposed synchronous control selection
0: Disabled
1: Enabled
This function will be enabled in the profile mode. Setting "1" in other control modes
will trigger [AL. 37 Parameter error].
This function will be enabled in the standard control mode. Setting "1" in other
operation modes will trigger [AL. 37 Parameter error].
This function can be used when the scale measurement function is enabled. Setting
"1" when the scale measurement function is disabled will trigger [AL. 37 Parameter
error].
Setting "1" when the MR-D30 has been connected or the degree unit has been set
will trigger [AL. 37 Parameter error].
For details, refer to chapter 18,19,20.