NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
Never connect any voltages or signals to reserved terminals (marked with
"NC"). Reserved terminals may carry internal voltages.
The following figure shows the connection of the option board for digital I/O extension
TA5105-4DOT:
NOTICE!
Risk of malfunctions in the plant!
Only if L+/M of the CPU is available and the outputs are already configured in
the AB program, the outputs will switch on as soon as the UP/ZP is available.
This must be considered in the application planning.
NOTICE!
Risk of damaging the I/O module!
The outputs are not protected against short circuits and overload.
Never short-circuit or overload the outputs.
Never connect the outputs to other voltages.
Use an external fuse for the outputs.
The module provides several diagnosis functions, see Diagnosis
Ä
“Diagnosis” on page 61.
The meaning of the LEDs is described in the section State LEDs
Ä
“State LEDs” on page 62.
The module itself does not store configuration data. It receives its parameterization data from
the CPU module during power-up of the system.
Hence, replacing optional modules is possible without any re-parameterization via software.
The arrangement of the parameter data is performed with Automation Builder software.
I/O configura-
tion
Parameteriza-
tion
Device specifications
Processor modules > AC500-eCo
2022/01/313ADR010278, 3, en_US60