The arrangement of the parameter data is performed with Automation Builder software.
1. In the device tree, double-click the desired option board.
2. Select the “TA51xx Parameters” tab to edit the parameterization of the desired option
board.
1. In the device tree, double-click the desired option board.
2. Select the “Diagnosis” tab to view the diagnosis messages of the desired option board.
Table 30: Diagnosis messages
Device Severity Error
code
Description
Error Message Remedy
TA5110-2DI2DOT 11 1 Wrong or no board
plugged
Replace with correct func-
tional board
TA5110-2DI2DOT 11 2 Board defective Replace with correct func-
tional board
TA5110-2DI2DOT 11 3 Failed to set direction Replace with correct func-
tional board
TA5110-2DI2DOT 11 4 Parameter wrong Verify setting of parameter
“Run on config fault”
LED State Color LED = OFF LED = ON
Inputs I0...I1 Digital input Yellow Input is OFF Input is ON
Outputs O0...O1 Digital output Yellow Output is OFF Output is ON
Parameteriza-
tion
Diagnosis
State LEDs
Processor modules > AC500-eCo
2022/01/313ADR010278, 3, en_US68