Address Name / seng range / [default seng] Info
0x2631:050
(P400.50)
Select sequence (bit 0)
(Seq: Select. b0)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 03.00
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Select sequence (bit 0)" funcon.
Selecon bit with the valency 2
0
for bit coded selecon of a sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
•
The selected sequence is not started automacally.
•
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
•
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:051
(P400.51)
Select sequence (bit 1)
(Seq: Select. b1)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 03.00
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Select sequence (bit 1)" funcon.
Selecon bit with the valency 2
1
for the bit-coded selecon of a
sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
•
The selected sequence is not started automacally.
•
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
•
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:052
(P400.52)
Select sequence (bit 2)
(Seq: Select. b2)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 03.00
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Select sequence (bit 2)" funcon.
Selecon bit with the valency 2
2
for the bit-coded selecon of a
sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
•
The selected sequence is not started automacally.
•
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
•
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:053
(P400.53)
Select sequence (bit 3)
(Seq: Select. b3)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 03.00
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Select sequence (bit 3)" funcon.
Selecon bit with the valency 2
3
for the bit-coded selecon of a
sequence.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
Notes:
•
The selected sequence is not started automacally.
•
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is available.
•
For an edge-controlled start, the funcon "Start sequence"
0x2631:031 (P400.31) is available.
0 Not connected No trigger assigned (trigger is constantly FALSE).
Conguring the frequency control
Congure setpoint sources
Sequencer