Example for operang mode
In the following example, the digital inputs 2 and 3 are used for controlling the sequencer.
•
The analog input 1 is set as standard setpoint source.
•
The switch S1 starts the motor in the forward direcon of rotaon. The switch S1 in the
inial posion stops the motor again.
•
The buon S2 starts the sequence, the buon S3 aborts the sequence. Aer the aboron,
the normal setpoint control is acve again.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Buon S2 Start sequence
Buon S3 Abort sequence
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:031 (P400.31) Start sequence Digital input 2 [12]
0x2631:036 (P400.36) Abort sequence Digital input 3 [13]
0x2631:050 (P400.50) Select sequence (bit 0) Constant TRUE [1]
0x2634:001 (P420.01) Relay Sequencer controlled [100]
0x2634:002 (P420.02) Digital output 1 Sequencer controlled [100]
Segment and sequence conguraon
In this example, only the sequence 1 is used. The sequence consists of two steps (segment 1 and segment 2).
0x4026:001 (P801.01) Sequencer segment 1: Frequency setpoint 40 Hz
0x4026:002 (P801.02) Sequencer segment 1: Acceleraon/deceleraon 20 s
0x4026:003 (P801.03) Sequencer segment 1: Time 18 s
0x4026:004 (P801.04) Sequencer segment 1: Digital outputs 0x00
0x4027:001 (P802.01) Sequencer segment 2: Frequency setpoint 30 Hz
0x4027:002 (P802.02) Sequencer segment 2: Acceleraon/deceleraon 15 s
0x4027:003 (P802.03) Sequencer segment 2: Time 14 s
0x4027:004 (P802.04) Sequencer segment 2: Digital outputs 0x02 (only relay)
0x402E:001 (P822.01) End segment: Frequency setpoint 10 Hz
0x402E:002 (P822.02) End segment: Acceleraon/deceleraon 8 s
0x402E:003 (P822.03) End segment: Time 10 s
0x402E:004 (P822.04) End segment: Digital outputs 0x04 (only digital output 1)
0x4030:001 ... 0x4030:016
(P830.01 ... 16)
Sequence 1: Step 1 Segment 1 [1]
Sequence 1: Step 2 Segment 2 [2]
Sequence 1: Step 3 Skip step [0]
... ...
Sequence 1: Step 16 Skip step [0]
Sequencer basic sengs
0x4025 (P800.00) Sequencer mode Time operaon [1]
0x402F (P824.00) End of sequence mode Keep running [0]
0x4040 (P820.00) Start of sequence mode Restart sequencer [0]
Conguring the frequency control
Congure setpoint sources
Sequencer