Performing opmisaon with engineering tool
The following ow diagram shows the opmisaon process with an engineering tool
(e. g. »EASY Starter«):
b)
e)
Yes
No
Yes
Yes
NoNo
No
End
of the motor (non-energised)
Automatic calibration
d)
speed controller are initialised
Only motor and
b)
of the motor (energized)
Automatic identification
c)
coupling to the motor
• Mechanical load and its
Set manually:
coupling to the motor
• Mechanical load and its
• Motor control type
the motor nameplate)
• Motor data (e.g. according to data on
Set manually:
Lenze motor
connected?
possible?
(energized)
Identification
possible?
(energized)
Identification
required?
speed controller
Adjustment of
is selected
Motor from motor catalogue
a)
Start
Yes
a) The relevant motor data must be set rst. You benet from very precise motor equivalent circuit diagram data by selecng the motor from
the motor catalogue.
4Select motor from motor catalogue ^ 51
b) Manually set the motor data in accordance with the manufacturer's informaon / motor data sheet when a third-party motor is connected
to the inverter.
4Manual seng of the motor data^ 52
c) The speed controller must be rst reinialised alone if the load adjustment in the opmized system has changed.
4Tuning of the motor and the speed controller ^ 219
d) If the applicaon enables you to energise the system during the opmisaon procedure, carry out an automac idencaon. This proce-
dure results in the best possible parameter sengs.
4Automac motor idencaon (energized) ^ 216
e) If the applicaon does not enable you to energise the system during the opmisaon procedure, carry out an automac calibraon.
4Automac motor calibraon (non-energized) ^ 218
Conguring the motor control
Opons for opmising the control loops
214