Performing opmisaon with keypad
Since there is no access with the keypad to the motor catalogue, rst the motor data must be
set manually with the keypad according to the manufacturer data/motor data sheet. 4Man-
ual seng of the motor data ^ 52
The following ow diagram shows the opmisaon process with the keypad:
Yes
Yes No
No
End
d)
Automatic motor calibration
(non-energized)
c)
Automatic motor identification
(energized)
• Mechanical load and its coupling to the
motor
• Motor data (e.g. according to data on
the motor nameplate)
Set manually:
• Motor control type
a)
Lenze motor
connected?
Identification
(energized)
possible?
Start
a) Manually set the motor data in accordance with the manufacturer's informaon / motor data sheet when a third-party motor is con-
nected to the inverter.
4Manual seng of the motor data^ 52
c) If the applicaon enables you to energise the system during the opmisaon procedure, carry out an automac idencaon. This
procedure results in the best possible parameter sengs.
4Automac motor idencaon (energized)^ 216
d) If the applicaon does not enable you to energise the system during the opmisaon procedure, carry out an automac calibraon.
4Automac motor calibraon (non-energized)^ 218
Conguring the motor control
Opons for opmising the control loops
215