Restart of the communicaon
The communicaon needs to be restarted aer the EtherCAT conguraon is changed, so that
the changed sengs can take eect.
For restarng communicaon, there are two opons:
a)
Switch inverter o and on again.
b)
0x2360 (P508.00) Set = "Restart with current values [1]".
Parameter
Address Name / seng range / [default seng] Info
0x2360
(P508.00)
EtherCAT communicaon
(EtherCAT comm.)
From version 02.00
Restart communicaon.
When the device command has been executed successfully, the value
0 is shown.
0 No acon/no error Only status feedback
1 Restart with current values Restart communicaon with the current values.
10 In process Only status feedback
11 Acon cancelled
12 Fault
Conguring the network
EtherCAT
Commissioning
372