Power Simulator Settings for a Local End (or a Remote End if configured) to verify Metering
and Status:
Local End
Remote End
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
5A
0°
60.00
5A
180°
60.00
IB
5A
240°
60.00
5A
60°
60.00
IC
5A
120°
60.00
5A
-60°
60.00