EasyManua.ls Logo

RFL Electronics GARD 8000 - Page 134

RFL Electronics GARD 8000
647 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Commissioning
GARD 8000 SYS RFL Electronics
November 28, 2017 4-70 973.334.3100
4.6.4.15.1 internal faults
Phase to Phase Fault A B
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
4.5A
0°
60.00
IB
1A
180°
60.00
4.5A
180°
60.00
IC
0A
0°
60.00
0A
0°
60.00
Typical Trip Time +/-3ms
Solid State Output
Relay Output
Differential
15.50ms
18.80ms
High Set Trip
10.10ms
13.40ms
Phase to Phase Fault B C
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
0A
0°
60.00
0A
0°
60.00
IB
1A
180°
60.00
4.5A
180°
60.00
IC
1A
0°
60.00
4.5A
0°
60.00
Typical Trip Time +/-3ms
Solid State Output
Relay Output
Differential
15.70ms
19.10ms
High Set Trip
10.60ms
13.90ms
Phase to Phase Fault A C
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
4.5A
0°
60.00
IB
0A
0°
60.00
0A
0°
60.00
IC
1A
180°
60.00
4.5A
180°
60.00
Typical Trip Time +/-3ms
Solid State Output
Relay Output
Differential
15.40ms
18.90ms
High Set Trip
10.30ms
13.50ms

Table of Contents