Installation and Commissioning
GARD 8000 SYS RFL Electronics
November 28, 2017 4-72 973.334.3100
Phase to Ground Fault C G
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
0A
0°
60.00
0A
0°
60.00
IB
0A
240°
60.00
0A
240°
60.00
IC
1A
120°
60.00
4.5A
120°
60.00
Typical Trip Time +/-3ms
Solid State Output
Relay Output
Differential
15.50ms
18.80ms
High Set Trip
10.10ms
13.40ms
4.6.4.15.2 power simulator test plans - EXTERNAL FAULTS
3 Phase to Phase Fault A B C: Settings for a Local End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
15A
0°
60.00
IB
1A
240°
60.00
15A
240°
60.00
IC
1A
120°
60.00
15A
120°
60.00
3 Phase to Phase Fault A B C : Settings for a Remote End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
180°
60.00
15A
180°
60.00
IB
1A
60°
60.00
15A
60°
60.00
IC
1A
-60°
60.00
15A
-60°
60.00
Phase to Phase Fault A B: Settings for a Local End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
15A
0°
60.00
IB
1A
180°
60.00
15A
180°
60.00
IC
1A
0°
60.00
0A
0°
60.00