Installation and Commissioning
GARD 8000 SYS RFL Electronics
November 28, 2017 4-73 973.334.3100
Phase to Phase Fault A B: Settings for a Remote End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
180°
60.00
15A
180°
60.00
IB
1A
0°
60.00
15A
0°
60.00
IC
1A
0°
60.00
0A
0°
60.00
Phase to Phase Fault A C: Settings for a Local End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
15A
180°
60.00
IB
1A
0°
60.00
0A
0°
60.00
IC
1A
180°
60.00
15A
0°
60.00
Phase to Phase Fault AC: Settings for a Remote End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
180°
60.00
15A
180°
60.00
IB
1A
0°
60.00
0A
0°
60.00
IC
1A
0°
60.00
15A
0°
60.00
Phase to Ground Fault AG: Settings for a Local End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
15A
0°
60.00
IB
1A
0°
60.00
0A
0°
60.00
IC
1A
0°
60.00
0A
0°
60.00