EasyManua.ls Logo

RFL Electronics GARD 8000 - Page 138

RFL Electronics GARD 8000
647 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Commissioning
GARD 8000 SYS RFL Electronics
November 28, 2017 4-74 973.334.3100
Phase to Ground Fault A G: Settings for a Remote End
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
180°
60.00
15A
180°
60.00
IB
1A
0°
60.00
0A
0°
60.00
IC
1A
0°
60.00
0A
0°
60.00
Simulating External Trips using the provided test plans should not produce a Trip Condition!
4.6.4.16 TESTING BACK-UP OVERCURRENT FUNCTION:
1. Break the Communication Link.
2. Enable the ‘Back-up’ Setting on the webpage for ‘Current Differential Relay Backup
Settings.’
3. Enable ‘Overcurrent Backup.’
4. Program the Phase, Ground, and Timer Overcurrent settings as per the recommended Current
Differential Backup factory settings.
5. Setup a Power System Simulator for ‘Phase A’ to Ground Trips as shown below.
Pre-Fault Settings
Fault Settings
Source
Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
IA
1A
0°
60.00
5A
0°
60.00
IB
0A
240°
60.00
0A
240°
60.00
IC
0A
120°
60.00
0A
120°
60.00
6. Run the test.
7. The Current Differential Relay should restrain and not trip since the ‘Phase A’ amplitude is
simulated at 5A and the Overcurrent Backup Phase setting in the GARD is programmed for
8A.
8. Change ‘Phase A’ amplitude to 10A.
9. Run the test again.
10. The Current Diff relay should trip for ‘Phase A’ to Ground fault.
11. Typical Trip Times for this test are shown below.
Typical Trip Time +/-3ms
Solid State Output
Relay Output
Overcurrent Backup
12.20ms
15.40ms
After each test, the operation of the trip outputs can be verified by retrieving the Current Diff
Relay SOE Records, System SOE records, Current Diff Relay Oscillography records, and
Current Diff Relay Last Trip.

Table of Contents