Chassis Configuration Settings
GARD 8000 SYS RFL Electronics
April 1, 2012 7-26 973.334.3100
Bit Error Rate
This indicates the percentage of received bits in error compared to the total number of bits received.
This rate is an approximate value calculated from messages with CRC failures. As CRC detection
does not indicate the number of errors in a bad message, bit error rates above 5E-2 cannot be
accurately measured. This value is updated every 10 seconds based on the previous 110 seconds of
data. As there are only 7E 6 bits in 110 seconds, error rates less than 1E-6 cannot be accurately
measured.
Remote Service
This is a status indication that the TPS channel is Enabled for Remote Service, or Disabled for Remote
Service.
Tx Bus
Indicates which Comms Bus is being utilized for Tx communications.
Tx Direction
This is a status indication, which can be either A or B. In TPS the Tx Direction is forced to transmit on
Bus B. TPS will always transmit data on the B Bus.
TxAddress
Indicates the transmitter address for this TPS channel, between 0 and 255.
Rx Bus
Indicates which Comms Bus is being utilized for Rx communications.
Rx Direction
This is a status indication, which can be either A or B. In TPS the Rx Direction is forced to receive on
Bus A. TPS will always receive data from the A Bus.
Rx Address
Indicates the receiver address for this TPS channel, between 0 and 255.
Consecutive Timeslots
Displays the number of timeslots being used on the Comms Bus.
Run Logic/Logic/Firmware
This will indicate which files have been loaded into the GARD.
The other indicators at the bottom of this web screen read the information from the GARD, and are
normally factory installed.