If the UPS operaon is acve,
•
the device overload monitoring (i*t) is adapted accordingly.
•
the DC limit values are reduced.
•
the phase failure detecon is switched o.
•
the warning "UPS operaon acve" (error code 12672 | 0x3180) is output.
•
trigger "UPS operaon acve [118]" is set to TRUE. The trigger can be assigned to a digital
output.
•
bit 15 ("UPS operaon acve") in the inverter status word 2 0x2833 is set to "1".
Notes:
•
An addional limitaon of speed, current, etc. can be realised via the applicaon with the
"Parameter change-over“ funcon. ^ 525
Parameter
Address Name / seng range / [default seng] Info
0x2631:055
(P400.55)
Funcon list: Acvate UPS operaon
(Funcon list: Acv. UPS oper.)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger to the "Acvate UPS operaon" funcon.
Trigger = TRUE: Acvate UPS operaon.
Trigger = FALSE: no acon / deacvate funcon again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
Example for operang mode
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:055 (P400.55) Acvate UPS operaon Digital input 5 [15]
t
t
0 V
600 V
t
t
t
t
t
t
t
t
t
t
0x2D87
DC bus undervoltage warning
DC-bus undervoltage
Operation at UPS active
Error messages
1 x 230 V UPS voltage
Running [50]
Ready for operation [51]
Run
Digital input 5 [15]
Constant TRUE [1]
Digital input 1 [11]
UPS operation active [118]
Output signals
Status signals
DC-bus voltage
Activate UPS operation
Enable inverter
Input signals
3 x 400 V mains voltage
FunctionTrigger
The status signals can be assigned to digital outputs. 4Congure digital outputs^ 263
①
In order to change over to UPS operaon, a minimum delay is required.
Addional funcons
EOperaon with UPS