Address Name / seng range / [default seng] Info
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
•
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 536
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz), irrespecve of the
operang mode. Otherwise FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
72 Setpoint speed reached TRUE if frequency setpoint reached. Otherwise FALSE.
73 PID feedback = setpoint TRUE if the controlled variable fed back = process controller setpoint (±
in 0x404D:003 (P608.03) set hysteresis). Otherwise FALSE.
4Conguring the process controller^ 116
74 PID idle state acve TRUE if the inverter is in "PID idle state". Otherwise FALSE.
4Process controller idle state^ 124
75 PID MIN alarm acve TRUE if fed back variable (with acvated PID control) < MIN alarm
threshold. Otherwise FALSE.
•
Seng of MIN alarm threshold in 0x404D:001 (P608.01).
4Conguring the process controller^ 116
76 PID MAX alarm acve TRUE if the fed back variable (with acvated PID control) > MAX alarm
threshold. Otherwise FALSE.
•
Seng of MAX alarm threshold in 0x404D:002 (P608.02).
4Conguring the process controller^ 116
77 PID MIN-MAX alarm acve TRUE if no PID alarm is acve with acvated PID control (MIN alarm
threshold < fed back variable < MAX alarm threshold). Otherwise FALSE.
•
Seng of MIN alarm threshold in 0x404D:001 (P608.01).
•
Seng of MAX alarm threshold in 0x404D:002 (P608.02).
4Conguring the process controller^ 116
78 Current limit reached
TRUE if current motor current ≥ maximum current. Otherwise FALSE.
•
Display of the present motor current in 0x2D88 (P104.00).
•
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
•
Seng "Actual posive torque limit" in 0x2949:003 (P337.03).
•
Seng Actual negave torque limit in 0x2949:004 (P337.04).
Motor torque monitoring ^ 238
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
•
Monitoring threshold0x2636:008 (P430.08)
•
Monitoring condion0x2636:009 (P430.09)
The seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1^ 255
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
•
Monitoring threshold0x2637:008 (P431.08)
•
Monitoring condion0x2637:009 (P431.09)
The seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2^ 260
83 Load loss detected TRUE if actual motor current < threshold for load loss detecon aer
delay me of the load loss detecon has elapsed. Otherwise FALSE.
•
Display of the present motor current in 0x6078 (P103.00).
•
Seng Threshold in 0x4006:001 (P710.01).
•
Seng Delay me in 0x4006:002 (P710.02).
4Load loss detecon^ 212
84 Heavy load monitoring TRUE if the actual apparent current of the motor exceeds the threshold
for longer than the delay me. FALSE if the actual apparent current of
the motor falls below the threshold value minus 5% (hysteresis) Heavy
load monitoring ^ 241 .
100 Sequencer controlled (from version 03.00) The control is executed via the sequencer (according to the congura-
on of the digital outputs for the current segment).
4Segment conguraon ^ 93
I/O extensions and control connecons
Congure digital outputs
Relay output