Address Name / seng range / [default seng] Info
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 536
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz), irrespecve of the
operang mode. Otherwise FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
72 Setpoint speed reached TRUE if frequency setpoint reached. Otherwise FALSE.
73 PID feedback = setpoint TRUE if the controlled variable fed back = process controller setpoint (±
in 0x404D:003 (P608.03) set hysteresis). Otherwise FALSE.
4Conguring the process controller^ 116
74 PID idle state acve TRUE if the inverter is in "PID idle state". Otherwise FALSE.
4Process controller idle state^ 124
75 PID MIN alarm acve TRUE if fed back variable (with acvated PID control) < MIN alarm
threshold. Otherwise FALSE.
Seng of MIN alarm threshold in 0x404D:001 (P608.01).
4Conguring the process controller^ 116
76 PID MAX alarm acve TRUE if the fed back variable (with acvated PID control) > MAX alarm
threshold. Otherwise FALSE.
Seng of MAX alarm threshold in 0x404D:002 (P608.02).
4Conguring the process controller^ 116
77 PID MIN-MAX alarm acve TRUE if no PID alarm is acve with acvated PID control (MIN alarm
threshold < fed back variable < MAX alarm threshold). Otherwise FALSE.
Seng of MIN alarm threshold in 0x404D:001 (P608.01).
Seng of MAX alarm threshold in 0x404D:002 (P608.02).
4Conguring the process controller^ 116
78 Current limit reached
TRUE if current motor current maximum current. Otherwise FALSE.
Display of the present motor current in 0x2D88 (P104.00).
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
Seng "Actual posive torque limit" in 0x2949:003 (P337.03).
Seng Actual negave torque limit in 0x2949:004 (P337.04).
Motor torque monitoring ^ 238
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monitoring threshold0x2636:008 (P430.08)
Monitoring condion0x2636:009 (P430.09)
The seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1^ 255
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monitoring threshold0x2637:008 (P431.08)
Monitoring condion0x2637:009 (P431.09)
The seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2^ 260
83 Load loss detected TRUE if actual motor current < threshold for load loss detecon aer
delay me of the load loss detecon has elapsed. Otherwise FALSE.
Display of the present motor current in 0x6078 (P103.00).
Seng Threshold in 0x4006:001 (P710.01).
Seng Delay me in 0x4006:002 (P710.02).
4Load loss detecon^ 212
84 Heavy load monitoring TRUE if the actual apparent current of the motor exceeds the threshold
for longer than the delay me. FALSE if the actual apparent current of
the motor falls below the threshold value minus 5% (hysteresis) Heavy
load monitoring ^ 241 .
100 Sequencer controlled (from version 03.00) The control is executed via the sequencer (according to the congura-
on of the digital outputs for the current segment).
4Segment conguraon ^ 93
I/O extensions and control connecons
Congure digital outputs
Relay output
265