Address Name / seng range / [default seng] Info
0x2640:009
(P415.09)
HTL input sengs: Filter me constant
(HTL inp. seng: Filter me)
0 ... [10] ... 10000 ms
From version 04.00
PT1 me constant for low-pass lter.
0x2641:001
(P416.01)
HTL input monitoring: Minimum frequency threshold
(HTL inp. monit.: Min.freq.thresh.)
-214748364.8 ... [0.0] ... 214748364.7 Hz
From version 04.00
Sengs for the minimum frequency threshold for the monitoring of the
HTL input.
0x2641:002
(P416.02)
HTL input monitoring: Minimum delay threshold
(HTL inp. monit.: Min.delay thres.)
0.0 ... [5.0] ... 300.0 s
From version 04.00
Sengs for the minimum deceleraon threshold for the monitoring of
the HTL input.
0x2641:003
(P416.03)
HTL input monitoring: Maximum frequency threshold
(HTL inp. monit.: Max.freq.thresh.)
-214748364.8 ... [0.0] ... 214748364.7 Hz
From version 04.00
Sengs for the maximum frequency threshold for the monitoring of the
HTL input.
0x2641:004
(P416.04)
HTL input monitoring: Maximum delay threshold
(HTL inp. monit.: Max.delay thres.)
0.0 ... [5.0] ... 300.0 s
From version 04.00
Sengs for the maximum deceleraon threshold for the monitoring of
the HTL input.
0x2641:005
(P416.05)
HTL input monitoring: Monitoring condions
(HTL inp. monit.: Monit. condion)
From version 04.00
Monitoring condion for HTL input.
If the selected condion is fullled, the response set in 0x2641:006
(P416.06) takes place.
1 Below minimum frequency Input frequency < minimum frequency threshold 0x2641:001 (P416.01)
longer than the deceleraon 0x2641:002 (P416.02).
2 Above maximum frequency Input frequency > maximum frequency threshold 0x2641:003 (P416.03)
longer than the deceleraon 0x2641:004 (P416.04).
3 Below min. or above max. frequency Input frequency < minimum frequency threshold 0x2641:001 (P416.01)
longer than the deceleraon 0x2641:002 (P416.02) OR input frequency >
maximum frequency threshold 0x2641:003 (P416.03) longer than the
deceleraon 0x2641:004 (P416.04).
0x2641:006
(P416.06)
HTL input monitoring: Error response
(HTL inp. monit.: Error response)
From version 04.00
Selecon of the response to the triggering of the HTL input monitoring.
Associated error code:
28803 | 0x7083 - HTL input fault
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2642:001
(P115.01)
HTL input diagnoscs: Input frequency
(HTL inp. diag.: Input frequency)
Read only: x.x Hz
From version 04.00
Display of the current input value at the HTL input.
0x2642:002
(P115.02)
HTL input diagnoscs: Frequency setpoint
(HTL inp. diag.: Freq. setpoint)
Read only: x.x Hz
From version 04.00
Display of the current input value at the HTL input scaled as frequency
value.
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Velocity mode [-2]" is selected in 0x2860:001 (P201.01).
0x2642:003
(P115.03)
HTL input diagnoscs: PID setpoint
(HTL inp. diag.: PID setpoint)
Read only: x.xx PID unit
From version 04.00
Display of the current input value at the HTL input scaled as process con-
troller value.
The standard setpoint source for the reference value of PID control is
selected in 0x2860:002 (P201.02).
0x2642:004
(P115.04)
HTL input diagnoscs: Torque setpoint
(HTL inp. diag.: Torque setpoint)
Read only: x.x %
From version 04.00
Display of the current input value at the HTL input scaled as torque value
in percent.
100 % ≡ Motor rated torque 0x6076 (P325.00)
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Torque mode [-1]" is selected in 0x2860:003 (P201.03).
I/O extensions and control connecons
Congure digital inputs
Congure digital inputs DI3/DI4 for detecng a pulse train
251