Display code Short designaon Default seng Seng range Address Category
P606.01 Accel. me 1.0 s 0.0 ... 3600.0 s 0x4021:001 general
P606.02 Decel. me 1.0 s 0.0 ... 3600.0 s 0x4021:002 general
P607.xx PID inuence
P607.01 Acvaon me 5.0 s 0.0 ... 999.9 s 0x404C:001 general
P607.02 Mask out me 5.0 s 0.0 ... 999.9 s 0x404C:002 general
P608.xx PID alarms
P608.01 MIN alarm thrsh. 0.00 PID unit -300.00 ... 300.00 PID unit 0x404D:001 general
P608.02 MAX alarm thrsh. 100.00 PID unit -300.00 ... 300.00 PID unit 0x404D:002 general
P608.03 Bandw. feedback 2.00 % 0.00 ... 100.00 % 0x404D:003 general
P610.xx PID sleep mode
P610.01 Acvaon Disabled [0] Selecon list 0x4023:001 general
P610.02 Stop method Coasng [0] Selecon list 0x4023:002 general
P610.03 Freq. thresh. 0.0 Hz 0.0 ... 599.0 Hz 0x4023:003 general
P610.04 Feedback thresh. 0.00 PID unit -300.00 ... 300.00 PID unit 0x4023:004 general
P610.05 Delay me 0.0 s 0.0 ... 300.0 s 0x4023:005 general
P610.06 Recovery Setp. > P610.3 [0] Selecon list 0x4023:006 general
P610.07 Bandwidth 0.00 PID unit 0.00 ... 300.00 PID unit 0x4023:007 general
P610.08 Recovery thresh. 0.00 PID unit -300.00 ... 300.00 PID unit 0x4023:008 general
P615.xx Auto-rinsing
P615.01 Rinsing in idle Inhibited [0] Selecon list 0x4024:001 general
P615.02 Rinse interval 30.0 min 0.0 ... 6000.0 min 0x4024:002 general
P615.03 Rinse speed 0.0 Hz -599.0 ... 599.0 Hz 0x4024:003 general
P615.04 Rinse period 0.0 s 0.0 ... 6000.0 s 0x4024:004 general
P700.xx Device commands
P700.01 Load def. se. O / ready [0] Selecon list 0x2022:001 general
P700.03 Save user data O / ready [0] Selecon list 0x2022:003 general
P700.04 Load user data O / ready [0] Selecon list 0x2022:004 general
P700.05 Load OEM data O / ready [0] Selecon list 0x2022:005 general
P700.06 Save OEM data O / ready [0] Selecon list 0x2022:006 general
P700.07 Load par. set 1 O / ready [0] Selecon list 0x2022:007 general
P700.08 Load par. set 2 O / ready [0] Selecon list 0x2022:008 general
P700.09 Load par. set 3 O / ready [0] Selecon list 0x2022:009 general
P700.10 Load par. set 4 O / ready [0] Selecon list 0x2022:010 general
P700.11 Save par. set 1 O / ready [0] Selecon list 0x2022:011 general
P700.12 Save par. set 2 O / ready [0] Selecon list 0x2022:012 general
P700.13 Save par. set 3 O / ready [0] Selecon list 0x2022:013 general
P700.14 Save par. set 4 O / ready [0] Selecon list 0x2022:014 general
P700.15 Delete logbook O / ready [0] Selecon list 0x2022:015 general
P701.00 KP setp. incr. 1 1 ... 100 0x2862 general
P702.00 Scal.speed fact. 0.00 0.00 ... 650.00 0x4002 general
P703.00 KP status displ. 0x00000000 0x00000000 ... 0xFFFFFF00 0x2864 general
P704.xx DC braking
P704.01 Current 0.0 % 0.0 ... 200.0 % 0x2B84:001 general
P704.02 Hold me autom. 0.0 s 0.0 ... 1000.0 s 0x2B84:002 general
P704.03 Threshold autom. 0.0 Hz 0.0 ... 599.0 Hz 0x2B84:003 general
P704.04 Demagnet. me 100 % 0 ... 150 % 0x2B84:004 general
P704.05 Def. demag. me x ms - (Read only) 0x2B84:005 general
P704.06 DCbrk/inv.disab 0 0 ... 1 0x2B84:006 general
P705.00 KP language English [1] Selecon list 0x2863 general
P706.xx Brake management
P706.01 Operang mode Rfg stop (RFGS) [1] Selecon list 0x2541:001 general
P706.02 Acve threshold x V - (Read only) 0x2541:002 general
P706.03 Red. threshold 0 V 0 ... 100 V 0x2541:003 general
P706.04 Add.frequency 0.0 Hz 0.0 ... 10.0 Hz 0x2541:004 general
* Default seng depending on the size.