Address Designaon Default seng Category Data type Factor A M
0x2916
(P211.00)
Maximum frequency Device for 50-Hz mains:
50.0 Hz
Device for 60-Hz mains:
60.0 Hz
general U16 10 P -
0x2917
(P220.00)
Acceleraon me 1 5.0 s general U16 10 P rt
0x2918
(P221.00)
Deceleraon me 1 5.0 s general U16 10 P rt
0x2919
(P222.00)
Acceleraon me 2 5.0 s general U16 10 P -
0x291A
(P223.00)
Deceleraon me 2 5.0 s general U16 10 P -
0x291B
(P224.00)
Auto-changeover threshold of ramp 2 0.0 Hz general U16 10 P -
0x291C
(P225.00)
Quick stop deceleraon me 1.0 s general U16 10 P -
0x291E:001
(P226.01)
S-Ramp characterisc: Smoothing factor 0.0 % general U16 10 P r
0x291E:003
(P226.03)
S-Ramp characterisc: Stop threshold 10.0 % general U16 10 P -
0x291F:001
(P317.01)
Skip frequencies: Skip frequency 1 0.0 Hz general U16 10 P -
0x291F:002
(P317.02)
Skip frequencies: Skip bandwidth 1 0.0 Hz general U8 10 P -
0x291F:003
(P317.03)
Skip frequencies: Skip frequency 2 0.0 Hz general U16 10 P -
0x291F:004
(P317.04)
Skip frequencies: Skip bandwidth 2 0.0 Hz general U8 10 P -
0x291F:005
(P317.05)
Skip frequencies: Skip frequency 3 0.0 Hz general U16 10 P -
0x291F:006
(P317.06)
Skip frequencies: Skip bandwidth 3 0.0 Hz general U8 10 P -
0x291F:016 Skip frequencies: Status - (Read only) general U16 1 - -
0x291F:032 Skip frequencies: Input frequency x.xx Hz (Read only) general I32 100 - -
0x291F:033 Skip frequencies: Output frequency x.xx Hz (Read only) general I32 100 - -
0x2939
(P305.00)
Switching frequency 0 * general U8 1 P -
0x293A
(P116.00)
Actual switching frequency - (Read only) general U8 1 O t
0x2942:001
(P334.01)
Current controller parameters: Gain 42.55 V/A * MCTRL U32 100 P -
0x2942:002
(P334.02)
Current controller parameters: Reset me 4.50 ms * MCTRL U32 100 P -
0x2946:001
(P340.01)
Speed limitaon: Upper speed limit 0 vel. unit general I32 480000
/2
31
OP r
0x2946:002
(P340.02)
Speed limitaon: Lower speed limit 0 vel. unit general I32 480000
/2
31
OP r
0x2946:003
(P340.03)
Speed limitaon: Upper speed limit source Maximum frequency [0] general U8 1 P -
0x2946:004
(P340.04)
Speed limitaon: Lower speed limit source (-) Maximum frequency
[0]
general U8 1 P -
0x2946:005
(P340.05)
Speed limitaon: Upper frequency limit Device for 50-Hz mains:
50.0 Hz
Device for 60-Hz mains:
60.0 Hz
general I16 10 P -
0x2946:006
(P340.06)
Speed limitaon: Lower frequency limit Device for 50-Hz mains:
-50.0 Hz
Device for 60-Hz mains:
-60.0 Hz
general I16 10 P -
* Default seng depending on the size.