UPS MAINTENANCE
Eaton
®
9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 3 www.eaton.com/powerquality
62
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every
6 months by connecting the UPS to utility power. The internal batteries
charge to 90% capacity in less than 3 hours. However, Eaton
recommends that the batteries charge for 48 hours after long-term
storage. If optional EBMs are installed, see the recharge times listed in
Table 25 on page 90.
Check the battery recharge date on the shipping carton label. If the date
has passed and the batteries were never recharged, do not use the UPS.
Contact your service representative.
When to Replace Batteries
When the indicator illuminates, the audible alarm beeps, and the
“Battery Needs Service” alarm displays, the batteries may need
replacing. Contact your service representative to order new batteries.
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Batteries can be replaced easily without turning the UPS off or
disconnecting the load.
If you prefer to remove input power to change the batteries, see “UPS
Shutdown” on page 47.
Consider all warnings, cautions, and notes before replacing batteries.
W A R N I N G
S Servicing should be performed by qualified service personnel knowledgeable of batteries
and required precautions. Keep unauthorized personnel away from batteries.
S Batteries can present a risk of electrical shock or burn from high short circuit current.
Observe the following precautions: 1) Remove watches, rings, or other metal objects;
2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries,
4) Wear rubber gloves and boots.
S When replacing batteries, replace with the same type and number of batteries or battery
packs. Contact your service representative to order new batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.

Table of Contents

Other manuals for Hach sc200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hach sc200 and is the answer not in the manual?

Hach sc200 Specifications

General IconGeneral
Enclosure RatingNEMA 4X/IP66
Operating Temperature-20 to 60 °C (-4 to 140 °F)
Ambient Temperature-20 to 60 °C (-4 to 140 °F)
Enclosure MaterialPolycarbonate
Operating Humidity0 to 95% non-condensing
Relay OutputsUp to 4 SPDT relays
Storage Conditions-40 to 70 °C (-40 to 158 °F)
DisplayGraphical LCD
Inputs2 digital sensor inputs
Outputs4-20 mA
Power Supply100 to 240 VAC, 50/60 Hz
Analog Outputs2 or 4, 0/4-20 mA
CertificationsCE
CommunicationModbus RTU, HART
Dimensions144 x 144 mm
MountingPanel mount
Output4-20 mA
Power Requirements (Voltage)100 to 240 VAC
Warranty1 year
Weight1.2 kg

Related product manuals