Model 6 Motor Control Centers 80459-641-01E
Section 5—Operation 10/2012
© 1999–2012 Schneider Electric All Rights Reserved54
ENGLISH
Energizing the MCC
To energize the MCC:
1. Review the “Pre-operation Checklist” on page 53 before energizing.
2. Turn off all downstream loads, including distribution equipment and
other devices that are remote from the MCC.
3. Verify that all barriers, doors, and covers are closed before energizing
the equipment.
4. Energize the equipment in sequence, starting with the main devices, the
feeder devices next, and then the motor starter devices.
5. With all barriers in place and all unit doors closed and latched, turn on
the devices with a firm, positive motion.
6. After all disconnect devices are closed, loads such as lighting circuits,
starters, contactors, heaters, and motors may be energized.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
This equipment must only be installed and serviced by qualified
electrical personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Always use a properly rated voltage sensing device to confirm power is
off.
Replace all devices, doors, and covers before turning on power to this
equipment.
Review the “Pre-operation Checklist” on page 53, ensuring that all items
check out.
Failure to follow this instruction will result in death or serious injury.

Table of Contents

Other manuals for Hach sc200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hach sc200 and is the answer not in the manual?

Hach sc200 Specifications

General IconGeneral
Enclosure RatingNEMA 4X/IP66
Operating Temperature-20 to 60 °C (-4 to 140 °F)
Ambient Temperature-20 to 60 °C (-4 to 140 °F)
Enclosure MaterialPolycarbonate
Operating Humidity0 to 95% non-condensing
Relay OutputsUp to 4 SPDT relays
Storage Conditions-40 to 70 °C (-40 to 158 °F)
DisplayGraphical LCD
Inputs2 digital sensor inputs
Outputs4-20 mA
Power Supply100 to 240 VAC, 50/60 Hz
Analog Outputs2 or 4, 0/4-20 mA
CertificationsCE
CommunicationModbus RTU, HART
Dimensions144 x 144 mm
MountingPanel mount
Output4-20 mA
Power Requirements (Voltage)100 to 240 VAC
Warranty1 year
Weight1.2 kg

Related product manuals