Model 6 Motor Control Centers 80459-641-01E
Section 9—iMCC 10/2012
© 1999–2012 Schneider Electric All Rights Reserved86
ENGLISH
Table 15: Read/Write Registers
RAM
Address
Relative
Address
Code Description Range Default
C6 1B3 COM-LINE Command Line
Reset/run/stop, display lock,
network configuration enable
Motor Logic Plus Command Register (C6 hex)
01H Start/reset
02H Stop
03H Display lock
04H Display unlock
05H Network program enable
06H Network program disable
C8 1B4 Scale PowerLogic scale parameter
0, 1, 1–2; 16-bit signed word
(2s complement, read only)
Model dependent
CA 1B5 LV Low voltage threshold
170 V (450 V
)
- HV setting
435
CC 1B6 HV High voltage threshold LV setting - 528 V (660 V
) 500
CE 1B7 VUB Voltage unbalance threshold 2–15% or 999% 5%
D0 1B8 MULT CT/turns effective ratio 1 or 10–200 1
D2 1B9 OC Overcurrent threshold OL current range Min. rating
D4 1BA UC Undercurrent threshold 0.5 x OC Min. to OC Max., Off 0.8 x OC Min.
D6 1BB CUB Current unbalance threshold 2–25% or 999% 6%
D8 1BC TC Overcurrent trip class
5, J5, 10, J10, 15, J15, 20, J20,
30, J30
(J = Jam protection is enabled)
5 5 decimal
J5 133 decimal
10 10 decimal
J10 138 decimal
15 15 decimal
J15 143 decimal
20 20 decimal
J20 148 decimal
30 30 decimal
J30 158 decimal
DA 1BD RD1 Rapid cycle timer 2–500 seconds 10
DC 1BE RD2
Restart delay all faults except
undercurrent
2–500 minutes 8
DE 1BF RD3 Restart delay after undercurrent 2–500 minutes 20
E0 1C0 #RU # Restarts after undercurrent 0, 1, 2, 3, 4, A (Automatic)
RU Values
8.1 0–4 in decimal
8.2 A = 255 decimal
E2 1C1 #RF
# Restarts all faults except
undercurrent
0, 1, oc1, 2, oc2, 3, oc3, 4, oc4,
A, ocA
(0 = manual, A = continuous,
oc = automatic restart after RD2
expires)
RF Values
0 1 decimal
1 2 decimal
oc1 3 decimal
2 4 decimal
oc2 5 decimal
3 6 decimal
oc3 7 decimal
4 8 decimal
oc4 9 decimal
A 10 decimal
ocA 11 decimal
E4 1C2 UCTD Undercurrent trip delay 2–60 seconds 5
E6 1C3 GF Ground fault current threshold (0.4) AOL current range or Off 0.15 x Min.
E8 1C4 ADDR RS-485 slave address 01–99 1
Can only be viewed via network