Model 6 Motor Control Centers 80459-641-01E
Section 9—iMCC 10/2012
© 1999–2012 Schneider Electric All Rights Reserved80
ENGLISH
Operation This section contains pre-operation checklists, energizing procedures, and
remote and local programming procedures for TeSys™ T and
Motor Logic Plus
motor protection relays, PowerLogic™ Power Meter,
PowerLogic Circuit Monitor, Altivar™ drives, and Altistart™ soft starts.
Pre-operation Checklists To verify that the iMCC is operating properly, complete both of the following
checklists before energizing the equipment:
MCC Structure Complete the maintenance procedures beginning on page 55 and
continuing up to “Insulation Test” on page 66. This initial maintenance is
necessary to detect any shipping damage or loose connections. Do not
energize the MCC until initial maintenance is complete.
NOTE: The following maintenance procedures are not necessary before
energizing the MCC for the first time: Control Unit Removal, Stab
Assemblies, Starter Contacts and Barriers/Insulators.
Perform an insulation test on the MCC (see “Insulation Test” on
page 66).
If the MCC is equipped with ground fault protection, properly adjust and
test the ground fault protective device before energizing.
Remove all blocks or other temporary holding means from the electrical
devices.
Remove any secondary shunt bars from the current transformers. Do
not operate a current transformer with its secondary shunt bars
open-circuited.
Manually exercise all switches, circuit breakers, and other operator
mechanisms to ensure that they are properly aligned and operate freely.
Electrically exercise all electrically-operated switches, circuit breakers,
and other mechanisms (but not under load) to ensure that the devices
operate properly. This may require an auxiliary source of control power.
Verify proper interval and contact operation of the timers.
Set the Motor Logic Plus overcurrent setting to the maximum service
factor amperage of the motor to ensure that the proper overload
protection is provided. The Motor Logic Plus overcurrent threshold is set
at the lowest setting at the factory. Verify that all other settings are
optimized for the application.
The Parameter Settings Sheet lists all the parameters that have been
changed from the original, default settings. Any settings not shown on
this sheet will retain their original, default values.
Verify that all load and remote control connections have been made and
that they agree with the wiring diagrams provided.
Verify that all ground connections are made properly.
Install the covers and close the doors; verify that they are all properly
tightened.

Table of Contents

Other manuals for Hach sc200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hach sc200 and is the answer not in the manual?

Hach sc200 Specifications

General IconGeneral
Enclosure RatingNEMA 4X/IP66
Operating Temperature-20 to 60 °C (-4 to 140 °F)
Ambient Temperature-20 to 60 °C (-4 to 140 °F)
Enclosure MaterialPolycarbonate
Operating Humidity0 to 95% non-condensing
Relay OutputsUp to 4 SPDT relays
Storage Conditions-40 to 70 °C (-40 to 158 °F)
DisplayGraphical LCD
Inputs2 digital sensor inputs
Outputs4-20 mA
Power Supply100 to 240 VAC, 50/60 Hz
Analog Outputs2 or 4, 0/4-20 mA
CertificationsCE
CommunicationModbus RTU, HART
Dimensions144 x 144 mm
MountingPanel mount
Output4-20 mA
Power Requirements (Voltage)100 to 240 VAC
Warranty1 year
Weight1.2 kg