Model 6 Motor Control Centers 80459-641-01E
Section 9—iMCC 10/2012
© 1999–2012 Schneider Electric All Rights Reserved84
ENGLISH
Table 13: Motor Logic Plus Address Descriptions
Operation
Address
Code Description Notes
RAM Relative
Read only (all registers
are 16-bit words)
A0 1A0 VOLTAV Average voltage L–L V~
A2 1A1 IAVE Raw average current A (x100, x10, x1), multiplied by scale factor
A4 1A2 VUB Voltage unbalance 0–100%
A6 1A3 IUB Current unbalance 0–100%
A8 1A4 PFANGLE Power factor angle Degrees
AA 1A5 CAPTY Thermal capacity remaining 0–100%
AC 1A6 GFC Ground fault current A (x100, x10, x1), multiplied by scale factor
AE 1A7 ERCODE/TRIPRN Real time error (RTE) and trip indicator (TI) 8-bit nibble-coded RTE; 8-bit coded TI
B0 1A8 FH Fault history Fault order: 4th, 3rd, 2nd, Last
B2 1A9 PID Manufacture year/model and scale 8-bit year; 8-bit ID and scale
B4 1AA VA-C Line voltage A–C V~
B6 1AB VB-C Line voltage B–C V~
B8 1AC VA-B Line voltage A–B V~
BA 1AD IC Raw current phase C A (x100, x10, x1), multiplied by scale factor
BC 1AE IB Raw current phase B A (x100, x10, x1), multiplied by scale factor
BE 1AF IA Raw current phase A A (x100, x10, x1), multiplied by scale factor
C0 1Bo RD1 Remaining restart delay RD1
C2 1B1 RD2 Remaining restart delay RD2
C4 1B2 RD3 Remaining restart delay RD3
C6 1B3 COMLINE Command line code (address C6H) see Table 12 (write only)
C8 1B4 Scale PowerLogic
scale parameter (read only)
0, 1, 2; 16-bit signed word (2’s complement,
read only)
CA 1B5 LV Low voltage threshold 170 V~ to HV (600 V~ model; 450 V~ to HV)
CC 1B6 HV High voltage threshold LV to 528 V~ (600 V~ model; LV to 660 V~)
Read only (all registers
are 16-bit words)
CE 1B7 VUB Voltage unbalance threshold 2–15%, or 999 (off)
D0 1B8 MULT Effective turns ratio Determined by model
D2 1B9 OC Overcurrent threshold Current range of SSOLR
D4 1BA UC Undercurrent threshold 0.5 x OC Min. to OC Max., Off
D6 1BB CUB Current unbalance threshold 2–25%, or 999 (off)
D8 1BC TC Overcurrent trip class
5, J5, 10, J10, 15, J15, 20, J20, 30, J30
(J = Jam protection is enabled)
DA 1BD RD1 Rapid cycle timer 2–500 s
DC 1BE RD2 Restart delay RD2 2–500 min.
DE 1BF RD3 Restart delay RD3 2–500 min.
E0 1C0 #RU Restarts after UC 0, 1, 2, 3, 4, A
E2 1C1 #RF Number of restarts
0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, ocA
(0 = manual, A = continuous, oc = automatic
restart after RD2 expires)
E4 1C2 UCTD Undercurrent trip delay 2–60 s
E6 1C3 GF Ground fault threshold 0.15 x OC Min. to 0.2 x OC Max., Off
E8 1C4 ADDR RS-485 slave address 01–99
Required for PowerLogic software.