80459-641-01E Model 6 Motor Control Centers
10/2012 Section 9—iMCC
© 1999–2012 Schneider Electric All Rights Reserved
91
ENGLISH
Powerpact™ Circuit Breakers with
Micrologic™ Trip Units
Instructions for performing local or remote programming of the Micrologic
trip unit parameters can be found in Schneider Electric instruction bulletin
48940-313-01, PowerPact™ H-, J-, and L-Frame Circuit Breakers with
Micrologic™ Trip Units—User Guide.
Device Addressing Unless specified otherwise, MCC devices are assigned addresses starting
from 2.
Software
Configurable software—such as PowerLogic System Manager Software,
PowerSuite, or
Motor Logic
Plus Solutions—is available for communication
with your intelligent Model 6
iMCC
components. For setup, operating, and
maintenance instructions, consult the user manual included with your software
package.
Protocol
Maximum Number of
Addressable Nodes
Address Range Address to Avoid
Modbus 31 2–247 127
PROFIBUS 126 2–125 126
DeviceNet 64 2–62 63
CANopen 127 2–126 127