Table C-1. Remote Relay Module Specifications
POWER SUPPLY 12 VDC or 24 VDC
PERMISSIBLE RANGE 10.2 VDC to 28.8 VDC with less than 10% ripple
MAXIMUM CURRENT
CONSUMPTION 180 mA @ 24 VDC (pnp inputs)
220 mA @ 12 VDC (pnp inputs)
DIGITAL INPUTS 10 pnp (source) or npn (sink) inputs (NOTE 1)
NOMINAL
INPUT VOLTAGE 12 VDC or 24 VDC (NOTES 2 & 3)
INPUT VOLTAGES
FOR PNP (SOURCE) 12 VDC 0 to 3 VDC for Logic '0'
8 to 15 VDC for Logic '1'
24 VDC 0 to 5 VDC for Logic '0'
17 to 28.8 VDC for Logic '1'
INPUT CURRENT 4 mA @ 12 VDC
8 mA @ 24 VDC
INPUT IMPEDANCE 3 K Ω
RESPONSE TIME
(except high-speed inputs) 10 mS typical
GALVANIC ISOLATION None
INPUT CABLE LENGTH Up to 100 meters, unshielded
DIGITAL OUTPUTS 6 relay outputs, 230 VAC/ 12/24 VDC
OUTPUT TYPE SPST - NO relay
RELAY TYPE Takamisawa (Fujitsu) JY - 12H-K or
NAIS (Matsushita) JQ1A-12 V or
OMRON G6B-1114P-12 VDC
ISOLATION By relay
OUTPUT CURRENT 5 A max. (resistive load)
1 A max. (inductive load)
MAX. FREQUENCY 10 Hz
CONTACT PROTECTION External precautions required
DISPLAY STN, LCD display
ILLUMINATION LED yellow-green backlight
DISPLAY SIZE 2 lines, 16 characters long
CHARACTER SIZE 5 x8 matrix, 2.95 x 5.55 mm
KEYPAD Sealed membrane
NUMBER OF KEYS 15
C-2