Model 6 Motor Control Centers 80459-641-01E
Section 12—Insulation Resistance 10/2012
© 1999–2012 Schneider Electric All Rights Reserved104
ENGLISH
Section 12—Insulation
Resistance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
This equipment must only be installed and serviced by qualified
electrical personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Always use a properly rated voltage sensing device to confirm power is
off.
Replace all devices, doors, and covers before turning on power to this
equipment.
Follow the instructions in “Insulation Test” on page 66.
Failure to follow this instruction will result in death or serious injury.
NOTE: Disconnect all solid state
devices such as SPDs, drives, soft
starts, capacitors, filters, and circuit
monitors before performing
megohmmeter tests on the MCC.
Phase-To-Phase Phase-To-Ground
All Disconnects Open
Date A-B B-C C-A A-Ground B-Ground C-Ground
All Disconnects Closed
Date A-B B-C C-A A-Ground B-Ground C-Ground