Address Designaon Default seng Category Data type Factor A M
0x2633:002 Digital input debounce me: Digital input 2 1 ms general U8 1 P -
0x2633:003 Digital input debounce me: Digital input 3 1 ms general U8 1 P -
0x2633:004 Digital input debounce me: Digital input 4 1 ms general U8 1 P -
0x2633:005 Digital input debounce me: Digital input 5 1 ms general U8 1 P -
0x2633:006 Digital input debounce me: Digital input 6 1 ms Appl. I/O U8 1 P -
0x2633:007 Digital input debounce me: Digital input 7 1 ms Appl. I/O U8 1 P -
0x2634:001
(P420.01)
Digital outputs funcon: Relay Ready for operaon [51] general U8 1 P -
0x2634:002
(P420.02)
Digital outputs funcon: Digital output 1 Release holding brake
[115]
general U8 1 P -
0x2634:003
(P420.03)
Digital outputs funcon: Digital output 2 Fault acve [56] Appl. I/O U8 1 P -
0x2634:010
(P420.10)
Digital outputs funcon: NetWordOUT1 - bit 0 Ready for operaon [51] general U8 1 P -
0x2634:011
(P420.11)
Digital outputs funcon: NetWordOUT1 - bit 1 Not connected [0] general U8 1 P -
0x2634:012
(P420.12)
Digital outputs funcon: NetWordOUT1 - bit 2 Operaon enabled [52] general U8 1 P -
0x2634:013
(P420.13)
Digital outputs funcon: NetWordOUT1 - bit 3 Fault acve [56] general U8 1 P -
0x2634:014
(P420.14)
Digital outputs funcon: NetWordOUT1 - bit 4 Not connected [0] general U8 1 P -
0x2634:015
(P420.15)
Digital outputs funcon: NetWordOUT1 - bit 5 Quick stop acve [54] general U8 1 P -
0x2634:016
(P420.16)
Digital outputs funcon: NetWordOUT1 - bit 6 Running [50] general U8 1 P -
0x2634:017
(P420.17)
Digital outputs funcon: NetWordOUT1 - bit 7 Device warning acve
[58]
general U8 1 P -
0x2634:018
(P420.18)
Digital outputs funcon: NetWordOUT1 - bit 8 Not connected [0] general U8 1 P -
0x2634:019
(P420.19)
Digital outputs funcon: NetWordOUT1 - bit 9 Not connected [0] general U8 1 P -
0x2634:020
(P420.20)
Digital outputs funcon: NetWordOUT1 - bit 10 Setpoint speed reached
[72]
general U8 1 P -
0x2634:021
(P420.21)
Digital outputs funcon: NetWordOUT1 - bit 11 Current limit reached [78] general U8 1 P -
0x2634:022
(P420.22)
Digital outputs funcon: NetWordOUT1 - bit 12 Actual speed = 0 [71] general U8 1 P -
0x2634:023
(P420.23)
Digital outputs funcon: NetWordOUT1 - bit 13 Rotaonal direcon
reversed [69]
general U8 1 P -
0x2634:024
(P420.24)
Digital outputs funcon: NetWordOUT1 - bit 14 Release holding brake
[115]
general U8 1 P -
0x2634:025
(P420.25)
Digital outputs funcon: NetWordOUT1 - bit 15 Inverter disabled (safety)
[55]
general U8 1 P -
0x2635:001
(P421.01)
Inversion of digital outputs: Relay Not inverted [0] general U8 1 P -
0x2635:002
(P421.02)
Inversion of digital outputs: Digital output 1 Not inverted [0] general U8 1 P -
0x2635:003
(P421.03)
Inversion of digital outputs: Digital output 2 Not inverted [0] Appl. I/O U8 1 P -
0x2635:010 Inversion of digital outputs: NetWordOUT1.00 Not inverted [0] general U8 1 P -
0x2635:011 Inversion of digital outputs: NetWordOUT1.01 Not inverted [0] general U8 1 P -
0x2635:012 Inversion of digital outputs: NetWordOUT1.02 Not inverted [0] general U8 1 P -
0x2635:013 Inversion of digital outputs: NetWordOUT1.03 Not inverted [0] general U8 1 P -
0x2635:014 Inversion of digital outputs: NetWordOUT1.04 Not inverted [0] general U8 1 P -
0x2635:015 Inversion of digital outputs: NetWordOUT1.05 Not inverted [0] general U8 1 P -
0x2635:016 Inversion of digital outputs: NetWordOUT1.06 Not inverted [0] general U8 1 P -
0x2635:017 Inversion of digital outputs: NetWordOUT1.07 Not inverted [0] general U8 1 P -