BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve, or test products for compliance with ASHRAE standards.
Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International and the BACnet Testing Labratories (BTL). BTL is a registered trademark of BACnet International.
Reliable Controls Corporation
.
120 Hallowell Road
.
Victoria
.
BC
.
V9A 7K2
.
Canada
.
Toll Free 1(877) 475-9301
.
Tel (250) 475-2036
.
Fax (250) 475-2096
.
www.reliablecontrols.com
4/6
SUBMITTAL
MACH-ProWebSys
™
RELIABLE CONTROLS
®
MACH-SYSTEM
BACnet
®
Protocol Implementation Conformance Statement
Model # Product Name
MPW-S MACH-ProWebSys
™
*
*
Protocol Revision 135-2008, Firmware Version 7.50
BACnet Standard Device Profile
Product Device Profile
MACH-ProWebSys
™
BACnet Building Controller (B-BC)
BACnet Operator Workstation (B-OWS)
Segmentation Capability
Segmentation Type Supported Window Size
Able to transmit segmented messages Yes 1
Able to receive segmented messages Yes 1
Data Link Layer Options
Data Link Options
Ethernet (ISO 8802-3)
BACnet/IP x 2
MS/TP Master 9600, 19200, 38400, 76800
Point-To-Point 9600, 19200, 38400, 57600, 115200
Device Address Binding
Static Binding Supported No
Broadcast Capability
BACnet/IP Broadcast Management Device (BBMD)
Yes, supports registration by foreign devices.
Networking Options
Router Options
BACnet/IP1 <-> BACnet/IP2 BACnet/IP2 <-> MS/TP-Net
BACnet/IP1 <-> Ethernet BACnet/IP2 <-> PTP
BACnet/IP1 <-> MS/TP-Net Ethernet <-> MS/TP-Net
BACnet/IP1 <-> PTP Ethernet <-> PTP
BACnet/IP2 <-> Ethernet MS/TP-Net <-> PTP
Character Sets
Character Sets Supported ANSI X3.4
Supported BIBBs
Supported BIBBs BIBB Name
DS-RP-A Data Sharing-ReadProperty-A
DS-RP-B Data Sharing-ReadProperty-B
DS-RPM-A Data Sharing-ReadProperyMultiple-A
DS-RPM-B Data Sharing-ReadProperyMultiple-B
DS-WP-A Data Sharing-WriteProperty-A
DS-WPM-A Data-Sharing-WritePropertyMultiple-A
DS-WP-B Data Sharing-WriteProperty-B
DS-WPM-B Data Sharing-WriteProperyMultiple-B
DS-V-A Data-Sharing-View-A
DS-M-A Data-Sharing-Modify-A
DS-COV-A Data Sharing-COV-A
DS-COV-B Data Sharing-COV-B
DS-COVU-A Data Sharing-COV-Unsolicited-A
DS-COVU-B Data Sharing-COV-Unsolicited-B
AE-N-A Alarm and Event-Notification-A
AE-N-E-B Alarm and Event-Notification External-B
AE-N-I-B Alarm and Event-Notification Internal-B
AE-ACK-A Alarm and Event-ACK-A
AE-ACK-B Alarm and Event-ACK-B
AE-ASUM-B Alarm and Event-Alarm Summary-B
AE-ESUM-B Alarm and Event-Enrollment Summary-B
AE-INFO-B Alarm and Event-Information-B
AE-AS-A Alarm and Event Management-Alarm Summary View-A
AE-VM-A Alarm and Event Management-View and Modify-A
AE-VN-A Alarm and Event-View Notification-A
SCHED-VM-A Schedule-View and Modify-A
SCHED-I-B Scheduling-Internal-B
SCHED-E-B Scheduling-External-B
T-V-A Trending-View-A
T-VMT-I-B Trending-Viewing and Modifying Trends Internal-B
T-VMT-E-B Trending-Viewing and Modifying Trends External-B
T-ATR-B Trending-Automated Trend Retrieval-B
T-VMMV-I-B Trending-Viewing and Modifying Multiple Value Internal-B
T-VMMV-E-B Trending-Viewing and Modifying Multiple Value External-B
T-AMVR-B Trending-Automated Multiple Value Retrieval-B
DM-DDB-A Device Management-Dynamic Device Binding-A
DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-B Device Management-Dynamic Object Binding-B
DM-DCC-B Device Management-Device Communication Control-B
DM-ATS-A Device Management-Manual Time Synchronization-A
DM-MTS-A Device Management-Automatic Time Synchronization-A
DM-TS-A Device Management-Time Synchronization-A
DM-TS-B Device Management-Time Synchronization-B
DM-UTC-A Device Management-UTCTimeSynchronization-A
DM-UTC-B Device Management-UTCTimeSynchronization-B
DM-RD-B Device Management-Reinitialize Device-B
DM-BR-B Device Management-Backup and Restore-B
DM-R-B Device Management-Restart-B
DM-LM-A Device Management-List Manipulation-A
DM-LM-B Device Management-List Manipulation-B
DM-OCD-B Device Management-Object Creation and Deletion-B
NM-RC-B Network Management-Router Configuration-B