SUBMITTAL
SPACE-Sensor
™
Temperature
RELIABLE CONTROLS
®
MACH-SYSTEM
Aesthetically designed to complement any
decor, the Reliable Controls
®
SPACE-
Sensor
™
Temperature (SST) series
provides a traditional temperature sensor
solution and a wide array of options to
help you achieve comfort. The base model
SST contains a thermistor temperature
sensor. The CO
2
models feature a 0–2000
ppm 1–4 VDC CO
2
sensor. The OC models
feature a Passive Infrared Radiation (PIR)
motion sensor. The O models feature a
single button momentary contact override
button with backlight (on -L models) driven
from a universal output. The UD models
feature custom silicon rubber up/down
setpoint adjust buttons. The -S models
feature a 20k slider for setpoint adjust and
the -J models feature an RJ-11 jack for laptop
communications. Available in Warm Gray
(standard) or Solid White enclosure.
TECHNICAL SPECIFICATIONS
Project:
Engineer:
Approved by:
SST 06/06/12 TKB © 2012 Reliable Controls Corporation
1/3
DIMENSIONS
The CO
2
sensor employed in the
SST uses an ABC calibration
(Automatic Baseline Correction). The
calibration requires up to 3 weeks
to self-calibrate without interruption.
The calibration algorithm tracks the
lowest reading over a 7-day interval
to slowly correct long-term drift away
from acceptable fresh-air values of
between 400-450 ppm CO
2
. The
override and Up/Down buttons are
monitored by the controller using the
same input and same two wires as the
temperature sensor, in conjunction
with the Control-BASIC SENSOR-ON
and SENSOR-OFF functions.
Supply Voltage
5 VDC @ 20 mA from controller
9–12 VDC, 200 mA (2 Watts) from separate power supply for CO
2
models
(PS-VDC recommended)
9–12 VDC, 5 mA from separate power supply for OC models
Temperature Specifications
Dedicated 10k thermistor onboard
Range: 0 °C to 40 °C (32 °F to 104 °F)
± 0.1 °C (0.18 °F) resolution
User calibrated to ± 0.1 °C (0.18 °F) accuracy
CO
2
Sensor Specifications
NDIR sensor with auto calibration
1-4 VDC output (use table in range)
0–2000 ppm
Accuracy ± 30 ppm 5% of measured value
Occupancy Sensor Specifications
Passive Infrared Radiation (PIR) sensor
64 detection zones
100
o
horizontal / 82
o
vertical
5 m (16.4 ft.) max. detection distance
Buttons
Models with the -O option feature a custom silicon rubber override button
Models with the -L option feature an LED illuminated override button
Models with the -UD option feature custom silicon rubber up/down adjust buttons
Dimensions
12 cm L x 7 cm W x 2.4 cm H (4
3
/4” L x 2
3
/4” W x
15
/16” H)
Weight
0.09 kg (0.195 lb.)
Ambient Limits
2SHUDWLQJÝ&WRÝ&Ý)WRÝ)
6KLSSLQJÝ&WRÝ&Ý)WRÝ)
Humidity: 10% to 90% RH non-condensing