C. Control
1. With coils arranged for series airflow, a separate control is required on each bank, or coil, in the
direction of airflow.
2. On high-pressure installations, a two-position steam valve with a face and bypass arrangement is
preferred where modulating control is required.
3. Modulating valves must be sized properly—DO NOT OVERSIZE