48049-251-01 M-frame Circuit Breakers
02/2006
© 2003–2006 Schneider Electric All Rights Reserved
3
ENGLISH
2. Place circuit breaker on I-Line pan with jaws
(A) pushed against bus
Figure 4: Place Circuit Breaker on Pan
3. Insert long-shanked slotted screwdriver (A)
into slot. Rack circuit breaker onto bus.
Figure 5: Start Racking Circuit Breaker onto Bus
4. Insert second screwdriver (A) into bottom
slot. Rack circuit breaker further onto bus,
using alternate screwdrivers until circuit
breaker jaws completely engage bus bars
and mounting screws align with teardrop
opening in pan.
Figure 6: Rack Circuit Breaker Completely onto Bus
5. Tighten all mounting bracket screws (A)
firmly without bending mounting bracket.
Figure 7: Tighten Mounting Bracket Screws