SmartAXIS Touch User's Manual 29-11
1 Touch
29
SmartAXIS Specifications
Operating Range
● Output Specifications
Relay Output Specifications
■ FT1A-*12RA
Output Delay
Sink Input (I0 to I5) Source Input
Shared Digital/Analog Input (I6, I7)
2.7mA
5.3mA
Input Current (mA)
5V
15V
24V
Transition Area
ON Area
Input Voltage (V DC)
28.8V
0.9mA
4.4mA
OFF Area
-3.0mA
-6.2mA
Input Current (mA)
5V
15V
24V
Transition Area
ON Area
Input Voltage (V DC)
28.8V
-1.0mA
-5.2mA
OFF Area
ON Area
5V
15V
24V
28.8V
OFF Area
Transition Area
Input Current (mA)
0.2mA
0.37mA
0.06mA 0.3mA
Input Voltage (V DC)
No. of Outputs (Terminal No.) 4 (Q0 to Q3)
Output Type 1a contact
Maximum Load Current 10A
Minimum Switching Load 10 mA/5V DC (reference value)
Initial Contact Resistance 100 m max. (1A, 6V DC)
Electrical Life 100,000 operations min. (rated load 1,800 operations/hour)
Mechanical Life 20,000,000 operations min. (no load 18,000 operations/hour)
Rated Load 250V AC/10A, 30V DC/10A
Dielectric Strength
Between output
terminal and
internal circuit
2,300V AC 5mA, 1 minute
Between output
terminals (COMs)
Status Display Device Monitor screen (LCD display)
OFF delay: 330 msec max.
Chatter: 6 msec max.
ON delay: 6 msec max.
Command
Output Relay Status
ON
OFF
ON
OFF