SmartAXIS Touch User’s Manual 16-3
2 Data Storage Area Configuration Procedure
16
Data Storage Area
This section describes the configuration procedure for the data storage area.
1 On the Configuration tab, in the System Setup group, click Data Storage Area.
The Data Storage Area Management dialog box is displayed.
2 Specify the amount of Alarm Log data to save in the data storage area in Number of Stored Data for Alarm Log
(0 to 5011).
3 Specify the amount of Operation Log data to save in the data storage area in Number of Stored Data for
Operation Log (0 to 3579).
4 Specify the amount of Data Log data per device to save in the data storage area in Number of Stored Data for
Data Log per Device (0 to 12528).
5 Specify the number of HMI Keep Register (LKR) addresses in Number of HMI Keep Register (LKR) (1024 to
8192).
6 Specify the number of HMI Keep Relay (LK) addresses in Number of HMI Keep Relay (LK) (1024 to 8192).
7 Click OK.
The Data Storage Area Management dialog box closes.
This concludes configuring the data storage area.
2 Data Storage Area Configuration Procedure

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC SmartAXIS Touch FT1A Series and is the answer not in the manual?

IDEC SmartAXIS Touch FT1A Series Specifications

General IconGeneral
BrandIDEC
ModelSmartAXIS Touch FT1A Series
CategoryController
LanguageEnglish

Related product manuals